CORRECTION FACTORS â ENTERING AIR HEATING EAT DB (F) 60 65 68 70 75 80 TC Input Power THA 1.011 1.004 1.002 1.000 0.996 0.991 0.989 0.994 0.997 1.000 1.007 1.018 1.007 1.004 1.002 1.000 0.995 0.990 EAT WB (F) 60 65 66.2 67 70 75 COOLING Sensible Capacity Entering Dry Bulb (F) 70 75 80 80.6 85 90 95 Power Input THR 0.889 0.692 0.645 0.613 â â 1.087 0.884 0.838 0.806 0.683 â * 1.085 1.036 1.000 0.879 0.676 * 1.108 1.059 1.027 0.902 0.698 * * 1.231 1.199 1.077 0.866 * * * * 1.274 1.068 * * * * 1.415 1.266 0.964 0.988 0.995 1.000 1.016 1.037 0.902 0.967 0.985 1.000 1.046 1.106 TC 0.893 0.964 0.983 1.000 1.049 1.118 *Sensible Capacity equals total capacity. CORRECTION FACTORS â AIRFLOW % OF NOMINAL AIRFLOW TC 75% 81% 88% 94% 100% 106% 113% 0.951 0.964 0.979 0.990 1.000 1.010 1.019 DB EAT SC TC THA THR â â â â â â COOLING CORRECTIONS Input SC Power 0.860 0.963 0.894 0.973 0.936 0.984 0.969 0.992 1.000 1.000 1.033 1.008 1.069 1.016 THR 0.952 0.965 0.979 0.990 1.000 1.010 1.019 HEATING CORRECTIONS Input TC THA Power 0.990 1.054 0.966 0.993 1.035 0.977 0.996 1.019 0.987 0.998 1.008 0.994 1.000 1.000 1.000 1.002 0.994 1.005 1.003 0.988 1.011 LEGEND Dry Bulb Entering Air Temperature (F) Sensible Capacity Total Capacity Total Heat of Absorption Total Heat of Rejection 50KQL CONSOLE BLOWER PERFORMANCE 60 Hz 50KQL 07 09 12 15 19 RATED AIRFLOW (cfm) 240 300 350 400 460 AIRFLOW (cfm) Low Speed High Speed 190 240 300 340 400 240 300 350 400 460 NOTES: 1. Fan speed is field adjustable. 2. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v for 208-230 v units. 3. All units are ARI/ISO 13256-1 rated on high fan speed. 4. All units are designed and rated for zero external static pressure (non-ducted) application. 21